PLX31-EIP-ASCII4
- Download PLX Network & Wireless Cards Drivers
- Download Plx Network & Wireless Cards Driver Free
- Download Plx Network & Wireless Cards Driver Windows 10
- Download Plx Network & Wireless Cards Driver Download
Demo Network Performance Monitor and see firsthand how you can quickly detect, diagnose, and resolve network performance issues and outages today. Dive into SolarWinds® Network Performance Monitor (NPM), an easy-to-use, affordable network solution for the IT professionals who need scale and performance. Network Touch Screen Controllers; Network I/O Peripherals. Search EASE software and download QSC loudspeaker GLL & CLF files. EASE QSControl.net, Signal Manager. Download Firmware drivers for Windows, firmware, bios, tools, utilities.
ProSoft Technology’s EtherNet/IP™ to ASCII four-port communication gateway allows high-speed bi-directional data transfers between EtherNet/IP™-enabled PACs and ASCII devices such as weigh scales and barcode readers. The EtherNet/IP™ protocol driver supports the explicit messaging implementation. The gateway is userconfigurable as both a client and a server.
EtherNet/IP™ PACs include Rockwell Automation® ControlLogix® and CompactLogix™, as well as several Schneider Electric® controllers. Applications for this module are found in most industries, especially manufacturing, oil & gas, electrical power and food processing.
The gateway has several features that allow for simplified integration, reduced commissioning time and optimized performance.
Imágenes
Características y Beneficios
- Data prioritization: Multiple I/O connections allow you to set RPIs for status and/or control data, optimizing Ethernet bandwidth.
- Includes an embedded EDS Add-On Profile, allowing for simplified integration and reduced commissioning time.
- Includes a SD card slot (SD card optional) for storing configuration files. This can be used for disaster recovery.
- ProSoft Discovery Service: This utility allows your PC to see the gateway and change its default IP address without being on the same subnet.
- Secure module configuration via module switch (v1.04 and greater).
- Up to 10,000 16-bit registers can be used to exchange large amounts of data
Especificaciones
EtherNet/IP™ Specifications
Specification | Description |
Number of Class 3 Server Connections | 5 |
Supported PLC Types | PLC2, PLC5, SLC, CLX, CMPLX, MICROLX |
Supported Message Types | PCCC and CIP |
Class 3 Client Connections | Connected: 2 |
Number of Class 1 I/O Connections | 4 |
I/O connection sizes | 248/248 |
Max RPI time Rec driver download. | 5 ms per connection |
CIP Services Supported | 0x4C - CIP Data Table Read |
Command List | Support for 100 commands per Client, each configurable for command type, IP address, register to/from addressing and word/bit count |
Command Sets | PLC-2/PLC-3/PLC5 Basic Command Set |
ASCII Specifications
Transmit and Receive Buffer Size | 255 byte Transmit character length with 0 to 65535 millisecond delay between each transmitted character |
Hardware
Specification | Description |
Power Supply | 24 VDC nominal 10 to 36 VDC allowed Positive, Negative, GND Terminals |
Current Load | 24 VDC nominal @ 300 mA |
Operating Temperature | -25°C to 70°C (-13°F to 158°F) |
Storage Temperature | -40°C to 80°C (-40°F to 176°F) |
Shock | IEC 60068-2-27; 15G @ 11ms, 3-Axis (Operational) |
Vibration | IEC 60068-2-6; 5G @ 10 to 150 Hz |
Relative Humidity | 5% to 95% RH with no condensation |
Dimensions (H x W x D) | 5.38 x 1.99 x 4.38 in 13.67 x 5.05 x 11.13 cm |
LED Indicators | Configuration (CFG), Error (ERR), Power (PWR), Hardware Fault (FLT), Network Status (NS), EtherNet/IP™ Class I or Class III Connection Status (EtherNet/IP Only) Module Status (MS), Module Configuration Status (EtherNet/IP Only) Ethernet Communication Port Link/Activity, and 100 mbit Serial Communication Port Receive (RX) and Transmit (TX) |
Ethernet Port | 10/100Mbit half-duplex RJ45 Connector Electrical Isolation 1500 Vrms at 50 to 60 Hz for 60 seconds, applied as specified in section 5.3.2 of IEC 60950: 1991 Ethernet Broadcast Storm Resiliency is less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
Number of Serial Ports | 4 |
Serial Port Isolation | 2500 Vrms port signal isolation per UL 1577 serial port communication signal uses RF (Radio Frequency) modulation signal as isolation media, IC chip model is SiliconLabs Si844x (Si8440,Si8441,Si8442) |
Shipped With Each Unit | 2.5 mm screwdriver |
Descargas
PLX31-EIP-ASCII4 Datasheet | 900,93 kB | Última Modificación 21.12.2020 |
PLX30 Gateway Family FAQ | 569,86 kB | Última Modificación 07.10.2020 |
PLX3x User Manual | 6,23 MB | Última Modificación 01.12.2020 |
PLX30 Family CAD Files | 67,72 MB | Última Modificación 09.03.2017 |
ProSoft Configuration Builder | ||
Technical Note - Migrating from 5202-DFNT-ASCII4 to PLX31-EIP-ASCII4 | 1,06 MB | Última Modificación 19.12.2019 |
PLX3x EDS Files 1.4 | 52,73 kB | Última Modificación 04.01.2021 |
Vídeo
Download PLX Network & Wireless Cards Drivers
Quick Configuration of ProSoft's ASCII to EtherNet/IP Gateway Tutorial
Understanding Client, Server & I/O Messaging for Ethernet Networks
Download Plx Network & Wireless Cards Driver Free
Guide to bit-level data addressing in ProSoft Modbus modules
Guide to 32-bit data types in ProSoft Modbus modules
Download Plx Network & Wireless Cards Driver Windows 10
Certificaciones
Download Plx Network & Wireless Cards Driver Download
Declaration of Conformity (ATEX) | 348,50 kB | Última Modificación 28.10.2019 |
CB Safety | 327,80 kB | Última Modificación 31.03.2020 |
Korean KC Registration | 974,32 kB | Última Modificación 07.07.2020 |
UL/cUL; Class 1, Div 2 | 233,35 kB | Última Modificación 08.04.2019 |
Declaration of Conformity (RoHS/CE) | 359,34 kB | Última Modificación 18.12.2020 |
ODVA EtherNet/IP - Declaration of Conformity | 183,48 kB | Última Modificación 09.11.2020 |